Insulation:
R-Value:
R-value describes a material's ability to PREVENT heat loss,
while U defines the amount of heat that will be LOST through
a material or building component. R-Value is printed on
many products used in building construction, when those products
are intended for use in heat-losing areas. R-Value is a
relative measure, with no units. It is not like "pounds
of cement" or "gallons of oil". However,
it can still be used in deciding which material to use.
For example, if a one-inch thick sheet of material A has a value
of R5, and a one-inch sheet of B is rated R3, then A is a far
better insulator than B.
There are other considerations, of course. For example, extruded Polystyrene
(pink or blue), resists moisture well, while expanded Polystyrene
(white, beads are obvious) breaks down in moist situations.
On the question of cost, there may be a temptation to buy the
less expensive material, but the extra cost of the better insulator
will be repaid many times over during the life of the structure.
The table below presents R values for many common building materials.
Material R-Value
Air, perfectly still 5.95
Loose Cellulose 3.14
Fiberglass 3.70
Solid Glass 2.44
Corkboard 3.57
Foamed Urethane 5.56
Extruded Polystyrene 5.00
Expanded Polystyrene 3.85
Foil-faced Isocyanurate 7.67
Mineral wool 2.94
Insulating Roof Deck, 2" 2.78
Loose Fill, slag or rock 3.70
Soft Wood, Studs, etc 1.25
Hard Wood, oak, etc .90
Gypsum plaster .90
Masonry, Granite, Brick 1.00
U-value:
U-value is the more important measure for the designer, and
it has units. U-value allows us to calculate how much heat
will be lost by a wall or window, how big the boiler should be
for this house, and what we might save by upgrading the ceiling
insulation.
To see how U-value is used in building design, see Figuring
Heat Loss.
U-values are used for assemblies of materials,
or "systems", as with a double-glazed window, which
has two panes of glass, an air space inside, and two air films
clinging to the outside of the glass. The U-value of a “system” defines: the
number of BTUs that will pass through one square foot of that
system, in one hour, for every degree (F) difference between
the temperatures inside and outside of the system.
Heat energy will "drive itself" from the warmer area
toward the colder, and U-value tells how fast that will happen.
It is calculated by adding the inverse of the sum of all the
R-values in the assembly. A double-glazed window
would work out like this, starting with R-values of the components:
Glass 2
x 1/8 x 2.44 =.61
Inside air, 1/2" 1/2
x 5.95 = 2.98
2 Outside air films 1/16 x 5.95 = 1.49
------------
Sum
of R-values = 4.33
4.33 divided into 1 (the inverse) equals .23, and the U-value
of that window assembly is .23 BTUs per sq. ft. per hour per
Deg. F Diff.
Table of U-values:
Component U-Value
4-inch wall, un-insulated .131
4-inch wall, insulated .055
6-inch wall, insulated .032
Window, single .444
Window, double ** .251
Window, Triple .174
1.75" Wooden Door .175
1.75" insulated Outer Door .079
8" insulated Ceiling .029
** The air-space should be at least 1/2 inch wide. This U-value
differs slightly from the previous example, because the source
used a different value for air films.
Example:
Applying the values to a 4” insulated wall on the North
side of the house, 8 feet high and 60 feet long, with six double-glazed
Windows, each 2.5’ by 4’ with Indoor/Outdoor temps,
70°/20°.
Net wall: (8x60) - (6x2.5x4) x U x DT =
(480sf – 60sf) x.055 x 50° =1,155 BTUs/Hr
Windows:
{6x2.5x4) x U x DT=60sf x .251 x 50° = 753 BTUs/Hr
Total Heat loss of wall = 1908 BTUs/Hr
Note that the double-glazed window, in the North wall, with
no compensating solar gain, loses 5 times as much heat per square
foot as a typical 4” insulated wall.
|