FIGURING HEAT LOSS:
Below, we detail how to figure heat loss for any house or other
small building. Manual calculations can be boring. If
you want us to do it for you click here.
You can make a rough estimate of a building's heat loss by looking
at a year’s fuel bill and converting it to BTUs. Then apply
the data from the section on Cost of Fuels. Adjust as best you
can for hot-water usage, air conditioning, heat input from lighting,
etc. However, don't be satisfied with the results until you check
against the method outlined below.
For the levels of insulation and fenestration that you are considering:
A. What is the peak heating demand that the heater
must meet?
B. What is the total seasonal heating load?
A. Calculating Peak Load for the one-time
Extreme: To decide on the size of the heating unit that
your home should have, calculate the heat that will be lost through
all surfaces on a night almost equal to the coldest night on
record for the area. To explain "almost:": If
there have been four occasions when the temperature dropped to
ten degrees F below zero, and only one when it reached 15
below, then design for 10° below. The added cost of protecting
against one chance in hundreds is hard to justify.
Using the surface areas determined above, calculate the heat
loss based on the difference between 65° and the "almost
coldest” night. Starting with the example below, sketch
each of the walls, plus ceiling. Input the areas
and appropriate U values. Multiply out and add.
If you wish, you can set up a simple spreadsheet in Works that
speeds the process, and makes it easy to test different scenarios.
EXAMPLE:
Applying values to a 4" insulated wall at night, 8 feet
high and 60 feet long, with six double-glazed windows, each 2.5’ by
4’.
Indoor/Outdoor temps, 70o/20°F.Net wall: (8x60)-(6x2.5x4)
x U x T = (480sf – 60sf) x.055 x 50° = 1,155
BTUs/Hr
Windows: (6x2.5x4) x U x T = 60sf x .251 x 50° =
753 BTUs/Hr
Total Heat loss of wall = 1908 BTUs/Hr when outside air is at
20°F.
Notes:
For houses on slabs, assume heat loss through the (4"?)
slab for the outer two feet
all around the perimeter.
For houses on full foundation, assume heat loss through the
exposed concrete, plus as far below grade as the frost line extends
in your area. The rest of the basement wall, and its floor,
are considered to be fully insulated by the earth.
For the full-season calculation, if there is a wall that faces
within 20-25 degrees of Solar South, and it meets the specs outlined
in Design, remember not to include that wall in your heat-loss
total. Over a normal season, that south-facing wall
will gain more than it loses. If the building is rather old,
check the ceiling insulation thickness and condition to make
sure that the nominal value can still be used.
B. Calculating BTU load for a complete heating or
cooling season:
The name of this game, in case the alligators in the swamp have
distracted you, is to figure the cost of fuel using one level
of insulation or fenestration, and then see what you would save
by upgrading that, or by eliminating a skylight, or changing
fuel.
Same calculations as above, except:
For the expression “DT”, use the total seasonal
degree-Day figure for your area times 24 hours. The result is
the total BTU loss for the whole season. Use the Cost of Fuels
equation to see what space heating should cost you next year. |